ABB – Contactor AX205-30-11-84
- Description
Description
ABB – Contactor AX205-30-11-84
Manufactured: ABB
Product Type: Contactor
Product Tag: AX205-30-11-84
General Information
The ABB AX205-30-11-84 is a block-type, AC-operated power contactor designed primarily for controlling three-phase motors and switching electrical power circuits with an operational voltage of up to 1000 V AC. It has three normally open main poles and is supplied with one normally open and one normally closed auxiliary contact.
Features
- Three normally open main power contacts.
- One normally open and one normally closed auxiliary contact.
- AC-operated electromagnetic control coil.
- Suitable for controlling three-phase motors and power circuits up to 1000 V AC.
- Supports additional front-mounted or side-mounted auxiliary contact blocks and other accessories.
- Rated making capacity of 10 × Ie under AC-3 conditions.
- Rated breaking capacity of 8 × Ie under AC-3 conditions.
- Maximum electrical switching frequency of 300 operations per hour.
- Maximum mechanical switching frequency of 3,600 operations per hour.
- Mechanical durability of approximately 5 million operating cycles.
- Maximum operating altitude without derating: 3,000 m
Specification for AX205-30-11-84
Contact Configuration
Main Contacts:
- 3 Normally Open
- 0 Normally Closed
Auxiliary Contacts:
- 1 Normally Open
- 1 Normally Closed
Control Coil
Rated Control Circuit Voltage:
- 50 Hz: 110 V AC
- 60 Hz: 110–120 V AC
Main Circuit
Maximum Rated Operational Voltage: 1000 V AC
Rated Insulation Voltage, Ui: 690 V
Rated Impulse Withstand Voltage, Uimp: 8 kV
Rated Frequency: 50/60 Hz
Rated Operational Current — AC-3 Motor Duty
- 220/230/240 V: 205 A
- 380/400 V: 205 A
- 415 V: 205 A
- 440 V: 185 A
- 500 V: 170 A
- 690 V: 170 A
These AC-3 ratings apply at an ambient temperature close to the contactor of no more than 55 °C.
Rated Operational Power — AC-3 Motor Duty
- 220/230/240 V: 59 kW
- 380/400 V: 110 kW
- 415 V: 110 kW
- 440 V: 90 kW
- 500 V: 110 kW
- 690 V: 132 kW
Rated Operational Current — AC-1 Resistive Duty
At 690 V:
- 40 °C: 275 A
- 55 °C: 250 A
- 70 °C: 180 A
Short-Time Withstand Current
At 40 °C, in free air and starting from a cold state:
- 1 second: 2,000 A
- 10 seconds: 1,500 A
- 30 seconds: 1,000 A
- 1 minute: 800 A
- 15 minutes: 320 A
Environmental Conditions
Storage Temperature: −40 to +70 °C
Operating Temperature without Thermal Overload Relay: −40 to +70 °C
Operating Temperature with Thermal Overload Relay: −25 to +55 °C
Maximum Altitude without Derating: 3,000 m
Applicable Standards
- IEC 60947-1
- IEC 60947-4-1
- EN 60947-1
- EN 60947-4-1