Description

ABB – Contactor AX150-30-11-81

Manufactured: ABB

Product Type: Contactor

Product Tag: AX150-30-11-81

General Information

The ABB AX150-30-11-81 is a block-type, three-pole AC-operated contactor designed for controlling three-phase motors and switching industrial power circuits. The contactor is supplied with one normally open and one normally closed auxiliary contact through a side-mounted auxiliary contact block.

For IEC AC-3 motor applications, the AX150 contactor is rated at 150 A and 75 kW at 380–400 V. The “-81” coil code identifies a 24 V AC control coil at both 50 Hz and 60 Hz.

Features

  • Three normally open main power poles.
  • One normally open and one normally closed auxiliary contact.
  • Side-mounted auxiliary contact block.
  • AC-operated electromagnetic control circuit.
  • 24 V AC coil at 50/60 Hz.
  • Suitable for three-phase motor control and industrial power switching.
  • Supports additional front-mounted and side-mounted accessories.
  • Rated AC-3 making capacity of 10 times the operational current.
  • Rated AC-3 breaking capacity of 8 times the operational current.
  • Maximum electrical switching frequency of 300 cycles per hour.
  • Maximum mechanical switching frequency of 3,600 cycles per hour.
  • Mechanical durability of approximately 10 million operating cycles.
  • Maximum operating altitude without derating of 3,000 m.

Specification for AX150-30-11-81

Contact Configuration

Main Contacts:

  • 3 Normally Open
  • 0 Normally Closed

Auxiliary Contacts Fitted:

  • 1 Normally Open
  • 1 Normally Closed

Control Coil

Rated Control Circuit Voltage:

  • 50 Hz: 24 V AC
  • 60 Hz: 24 V AC

Coil Operating Limit: 0.85–1.10 × rated control voltage under the specified operating conditions.

Main Circuit

Maximum Rated Operational Voltage, Ue: 1000 V

Rated Insulation Voltage, Ui: 1000 V

Rated Impulse Withstand Voltage, Uimp: 8 kV

Rated Frequency: 50/60 Hz

Rated Operational Current — AC-3

  • 220–240 V: 150 A
  • 380–400 V: 150 A
  • 415 V: 150 A
  • 440 V: 100 A
  • 500 V: 100 A
  • 690 V: 82 A

Rated Operational Power — AC-3

  • 220–240 V: 45 kW
  • 380–400 V: 75 kW
  • 415 V: 75 kW
  • 440 V: 59 kW
  • 500 V: 59 kW
  • 690 V: 75 kW

Rated Operational Current — AC-1

  • At 40 °C: 190 A
  • At 55 °C: 145 A
  • At 70 °C: 130 A

Short-Time Withstand Current

At 40 °C, in free air and starting from a cold state:

  • 1 second: 1,320 A
  • 10 seconds: 800 A
  • 30 seconds: 500 A
  • 1 minute: 350 A
  • 15 minutes: 175 A

Environmental Conditions

Operating Temperature with Thermal Overload Relay: −25 to +55 °C

Operating Temperature without Thermal Overload Relay: −40 to +70 °C

Storage Temperature: −40 to +70 °C

Maximum Altitude without Derating: 3,000 m

Applicable Standards

  • IEC 60947-1
  • IEC 60947-4-1
  • EN 60947-1
  • EN 60947-4-1